Wet Chemical Extinguishing System || NFPA 17A

Wet Chemical Extinguishing System

Wet Chemical Extinguishing System
Wet Chemical Extinguishing System

What is Wet Chemical Extinguishing System, its applications, and how it works?!

It’s a fire suppression system designed to provide fire protection for :-
  • Restaurant, commercial, and institutional hoods.
  • Plenums , ducts and filters with their associated cooking appliances.

System suppress fire by spraying the plenum area, the filters , cooking surfaces and exhaust duct system with a pre-determined flow rate by :

  • Cooling the grease surface.
  • React with the hot grease and forming a layer of soap like foam on the surface of the fat, this layer act as an insulation between the hot grease and the atmosphere, which helping to prevent the escape of combustible vapor.

We can define this system as a pre-engineered system (NFPA 17A 3.3.13), which mean having predetermined:-

  • Flow rates.
  • Nozzle pressure.
  • Quantities of extinguishing agent.
  • Specific pipe size.
  • Max. and min. pipe length.
  • Flexible hose specification.
  • Numbers of fittings.
  • Number and type of nozzles.

So the system should listed by a testing laboratory, max. and min. pipe lengths and number of fittings should be permitted to be expressed in equivalent feet (meter) of pipe. The hazard protected by these systems should limited as to type and size based on actual fire test, limitations on hazards that are permitted to be protected by these systems are contained in the manufacturer’s design , installation, and maintenance manual, which is part of listing of the system.


Wet Chemical Extinguishing System Components

1- Detectors

Wet Chemical Extinguishing System
Wet Chemical Extinguishing System
Fusible hear detector to be suitable for vapor and grease field, it consist of three components :-
  • Fusible link.
  • Fusible link holder (Bracket).
  • linkage.

2- Discharge Nozzle

Wet Chemical Extinguishing System
Nozzles
Nozzle is a device used to deliver the liquid agent with a specific flow rate and stream pattern, it shall have the followings spec.:-
  • An internal strainer or a separate strainer located immediately upstream the nozzle.
  • Made of a corrosion-resistance material , non-combustible material (Brass or Stainless Steel) or to be protected inside and outside with deformation.
  • Have a protective cover cap, to prevent the entrance of grease, vapor, moisture, environmental contaminants and other foreign materials get in pipes.
Nozzle shall be marked and identification for each application and flow rate.

3- Agent Cylinder

It’s a stainless tank with valve assembly, which containing the extinguishing agent, it comes in different sizes according to each manufacturers.

4- Extinguishing agent

A potassium carbonite based extinguishing agent designed specially to extinguish grease laden fires.

5- System Releasing Module

Is a fully mechanical head that can be connected directly or remotely to the system valve and its required for system actuation, system can actuate by three methods:-
  • Fusible heat detector.
  • Direct from cylinder head.
  • Remote pull station.

6- Actuation Cartridge

Wet Chemical Extinguishing System
Actuation Cartridge
It’s gas cartridge contain nitrogen or carbon dioxide used to expels the liquid agent from the agent cylinders (tanks) through the discharge piping.

7- Remote Mechanical Pull Station

Its connected to Releasing module to actuate the system, its required at the point of egress from the hazard area are being protected.

8- Shut-off gas valve

It’s used to shut off the flow of gas to the appliances upon actuation of the releasing module , and it comes with different size.

9- Shielded Cable

Wet Chemical Extinguishing System
Shielded Cable
It used to connect the fusible link system, gas valve, and/or remote pull station to the Systems Releasing Module, 1/16” stainless steel cable encased in a protective, flexible conduit.

Wet Chemical Extinguishing System design

First of all we are deal with a pre-engineered system, so must follow the manufacturers limitation according to their testing report.
We have to know well the hood components which as the followings:-

  • Ducts.
  • Plenum.
  • Cooking Appliance ( Fat Fryer, Stove , boiler , grill,…… etc.)
Wet Chemical Extinguishing System
Hood Components


To make a correct design we must divide our design to sub-section as following:-
  • Nozzle Type and Placement.
  • Tanks Capacity.
  • Actuation cartridge selection.
  • Distribution of pipe network.
  • Detection System.

1- Nozzle Type, Placement and aim point.

Selection of nozzle based on:-
  • Coverage area for the nozzle and applications area.
  • Application (duct, plenum, cooking appliances) so nozzles used for protecting duct differ from that used for protecting plenum. After selecting nozzle type, then define nozzle placement and aim point according to manufacturer design manual.

2- Tanks Capacity.

Selection of tank based on term (Flow Point).
Flow Point is a term used in system design to describe the flow capacity of each nozzle according to manufactures design manual , which used in determine the tank capacity. 
Example:-
Wet Chemical Extinguishing System
Wet Chemical Extinguishing System
Note that: Selection of nozzle type based on application area and nozzle coverage area, flow point for each nozzle according to nozzle type and manufacturer design manual.

Tank capacity category based on max. flow point for each cylinder, so tank selection will be based on the total flow point for the whole system.
Example:-
Wet Chemical Extinguishing System
Wet Chemical Extinguishing System

3 - Actuation cartridge selection. 

Actuation cartridge have different sizes, selection of based on the number of cylinders will actuated.

4 - Distribution of pipe network.

The max. and min. pipe length for each size agent cylinder is based on total internal pipe volume, regardless of the diameter of the pipe used. All piping parameter are based on total system piping and do not make a distinction between branches and supply line piping. all pipe connections have a limitation according to cylinders size based on manufacturer test report and design manual.

5 - Detection System.

Conduit runs, pulley, elbows and number of detection per system must be within the approved system guide line.

Minimum requirement for detection system is :-

  • At least one fusible link shall be installed within each exhaust duct opening in accordance with the manufacturing listing NFPA 17A 5.6.1.4
  • Other than appliances that a downdraft ventilation system a fusible link shall be provided above each protected appliance or in accordance with the extinguishing system manufacturer’s design, installation and maintenance manual NFPA 17A 5.6.15
  • In case of electrostatic precipitator presence, must install detector after and before it.

Selection of rating of fusible heat detector based on the max. ambient temperature and according to Table A.7.3.4.1 NFPA 17A.
Wet Chemical Extinguishing System
Wet Chemical Extinguishing System

References of Article:

NFPA 17A - 2017 edition: Standard for Wet Chemical Extinguishing Systems


Fire Protection Specialists
Keeping You Up To Code

25 comments:

  1. Dear sir
    i would like to take training of fire fighting system, do you giving online training also. my contact no. 0092 300 200 7070 from Pakistan. please reply me at my no

    ReplyDelete
  2. I wanted to thank you for this excellent read!! I definitely loved every little bit of it. I have you bookmarked your site to check out the new stuff you post. תכנון מערכות גילוי אש

    ReplyDelete
  3. Appreciate your short and crisp notes..looking forward for more and videos and other docs related to design
    with regards

    ReplyDelete
  4. I exactly got what you mean, thanks for posting. And, I am too much happy to find this website on the world of Google. sakurai release agent

    ReplyDelete
  5. Additionally, state wellbeing division studies of regular folks in New Mexico and California demonstrated that 2-6% individually, have been determined to have MCS and that 16% of regular people detailed and "surprising affectability to normal ordinary chemicals. tadalafil powder

    ReplyDelete
  6. Super-Duper site! I am Loving it!! Will come back again, Im taking your feed also, Thanks. Bromadol HCl

    ReplyDelete
  7. I have bookmarked your blog, the articles are way better than other similar blogs.. thanks for a great blog! ephedrine hcl powder

    ReplyDelete
  8. This is a great inspiring article.I am pretty much pleased with your good work.You put really very helpful information. Keep it up. Keep blogging. Looking to reading your next post. amphetamin kaufen

    ReplyDelete
  9. Thanks so much for this information. I have to let you know I concur on several of the points you make here and others may require some further review, but I can see your viewpoint. Chemical traders in Mumbai

    ReplyDelete
  10. EPTEX is the manufacturer, and they are actually expert of supporting each system from top to bottom. Each industrial powder coating oven can be customized to meet your company’s unique requirements. They can customize this to your particular specifications.

    ReplyDelete
  11. They should also have stellar online customer reviews. You can determine this by typing the company name into your search engine and going through the results. buy xyrem online Legit

    ReplyDelete
  12. Thanks very informative for us engineers to be updated..

    ReplyDelete
  13. Do you constantly feel the cold in the winter months? Looking to keep warm without increasing your heating bills? Find out which are the best portable heaters to help you enjoy that toasty warm feeling throughout the day and night. https://aboutheating.co.uk/

    ReplyDelete
  14. Not only are electric heaters convenient and great for heating rooms or personal spaces, they can be very safe, energy efficient, and cost-effective. Learn how to choose one here. https://heatyourhomeforless.co.uk/

    ReplyDelete
  15. Individuals who were getting their psoriasis drugs paid for through their insurance agency were being dropped off their protection plans. Despite the fact that protection transporters paid for natural's before 2012 low pay Medicaid Federal medical insurance patients actually didn't approach these drugs.
    pink peruvian flake

    ReplyDelete
  16. When shopping for a free standing wood stove, it's important to keep a few things in mind. First and foremost, you want one that is well-insulated. This will help to keep your home warm during cold months and cool during hot months.

    ReplyDelete
  17. A home security framework isn't only for residents in horror regions.
    http://www.alphasecuritemontreal.com/

    ReplyDelete
  18. Water restoration professionals can help identify and address potential hazards, such as electrical issues, that arise from water damage. fire damage restoration fort worth

    ReplyDelete
  19. Considering a heat pump water heater? It's an energy-efficient option worth exploring. water heater replacement lake worth fl

    ReplyDelete
  20. Don't overlook the importance of good lighting in your home improvement plans. water heater repair tacoma

    ReplyDelete
  21. A well-insulated home can reduce the frequency of water heater cycling. water heater replacement west monroe

    ReplyDelete
  22. Fire safety plans for high-rise buildings include specific evacuation procedures for upper floors.
    Fire Suppression Systems

    ReplyDelete
  23. Great insights on pediatric care! At Lifeguard Pediatrics in Warner Robins, GA, we also emphasize the importance of personalized and compassionate care for our young patients. It's crucial for parents to feel supported and informed about their child's health and wellness. Looking forward to more discussions on this vital topic.
    Visit:https://lifeguardpediatrics.com/

    ReplyDelete
  24. Hanging, this is interfacing with as you need to discover extra, I welcome to This is my page. rent dumpster

    ReplyDelete