Fire Protection of fire pump units

Protection of fire pump units

Protection of fire pump units
Protection of fire pump units

Required Separation of firefighting Pump Rooms:
  • For outdoor Fire Pump Units
Fire pump units that are outdoors shall be located at least 15.3 m away from any buildings and other fire exposures.
  • For Indoor Fire Pump Units in high rise building
fire pump units buildings shall be protected from surrounding occupancies by a minimum of 2-hour fire-rated construction or physically separated from the protected building by a minimum of 50 ft (15.3 m).
  • For Indoor Fire Pump Units in non-high-rise buildings 
fire pump rooms in non-high-rise buildings or in separate fire pump buildings shall be physically separated or protected by fire-rated construction in accordance with following table.


Protection of fire pump units
Protection of fire pump units

Required Fire Protection system for Pump Rooms:
  • For Fire Pump Rooms with Diesel Engines:
Fire pump buildings or rooms enclosing diesel engine pump drivers and day tanks shall be protected with an automatic sprinkler system installed in accordance with NFPA 13 as an Extra Hazard Group 2 occupancy.
  • For Fire Pump Rooms with Electric Drivers:
For buildings that are required to be sprinklered, fire pump rooms enclosing electric fire pump drivers shall be protected with an automatic sprinkler system installed in accordance with NFPA 13 as an Ordinary Hazard Group 1 occupancy.

For more information, please check the topics below:


Fire Protection of fire pump units
Fire Protection Specialists
Keeping You Up To Code


7 comments:

  1. An author must have a vast knowledge of vocabulary. The dictionary of a writer must be full of new english vocabulary to make their work more attractive. Use of new words makes their work more valuable and graceful.Fire Alarm System Requirements

    ReplyDelete
  2. Vancouver fire safety plans We are really grateful for your blog post. You will find a lot of approaches after visiting your post. I was exactly searching for. Thanks for such post and please keep it up. Great work.

    ReplyDelete
  3. A centrifuge is a piece of equipment, generally driven by an electric motor, though older models were hand spun, that puts an object in rotation around a fixed axis, applying a force perpendicular to the axis. pump refurbishment

    ReplyDelete
  4. Sprinkler systems are one of the most effective tools in controlling fires in buildings.
    Fire Suppression Systems

    ReplyDelete